SF6 Gas Insulated Bypass Switch for Distribution Applications
SF6 gas insulated bypass switch for compact distribution applications. Sealed insulated design and practical operation make it suitable for utility maintenance and engineering projects.
As a professional manufacturer of SF6 Gas Insulated Bypass Switch, we provide more cost-effective products. Whether you want to buy or become a distributor, you are welcome to contact us anytime.
SF6 gas insulated bypass switch is designed for power distribution applications that need compact structure, sealed insulation, and dependable switching performance. This SF6 gas insulated bypass switch supports maintenance transfer, controlled isolation, and utility project operation where a protected internal design is preferred. The equipment is suitable for customers seeking a combination of space efficiency and stable field use.
In engineering and utility environments, the SF6 gas insulated bypass switch can be applied to upgrade work, distribution branches, and live network support tasks. Its gas insulated arrangement helps support reliable performance while keeping the unit compact and practical for installation. The layout is built for users who value straightforward operation and a clean equipment profile.
For distributors, OEM buyers, and project contractors, this SF6 gas insulated bypass switch offers a practical solution for long-term supply and engineering cooperation. It is well matched to applications requiring dependable insulated design, convenient operation, and strong project adaptability.
Section |
Item | Detail | 12 kV | 24 kV |
| Model Selection | 200 A | Manual Operation | DPSW-FLW-12/T200-40 | DPSW-FLW-24/T200-40 |
| Model Selection | 200 A | Electric Operation | DPSW-FLW-12/200-40 | DPSW-FLW-24/J200-40 |
| Model Selection | 400 A | Manual Operation | DPSW-FLW-12/T400-40 | DPSW-FLW-24/T400-40 |
| Model Selection | 400 A | Electric Operation | DPSW-FLW-12/J400-40 | DPSW-FLW-24/J400-40 |
| Technical Specifications | Rated Current | — | 400/200 A | 400/200 A |
| Technical Specifications | Rated Frequency | — | 50/60 Hz | 50/60 Hz |
| Insulation Performance | Rated Impulse Withstand Voltage | Phase-to-Ground | 75 kV | 125 kV |
| Insulation Performance | Rated Impulse Withstand Voltage | Between Terminals of the Same Phase | 95 kV | 145 kV |
| Insulation Performance | Rated Power-Frequency Withstand Voltage | Phase-to-Ground | 42 kV | 64 kV |
| Insulation Performance | Rated Power-Frequency Withstand Voltage | Between Terminals of the Same Phase | 48 kV | 79 kV |
| Switching Current Capability | Load Current | — | 400/200 A | 400/200 A |
| Switching Current Capability | Magnetizing Current | — | 21 A | 21 A |
| Switching Current Capability | Cable Charging Current | — | 25 A | 25 A |
| Switching Current Capability | Line Charging Current | — | 1.5 A | 1.5 A |
| Technical Specifications | Rated Short-Time Withstand Current | — | 16 kA / 3 s | 16 kA / 3 s |
| Technical Specifications | Rated Closing Current | — | 50 kA | 50 kA |
| Gas Pressure | Rated Pressure | — | 0.5 ± 0.1 kgf/cm² | 0.5 ± 0.1 kgf/cm² |
| Gas Pressure | Explosion-Proof Pressure | — | 4–6 kgf/cm² | 4–6 kgf/cm² |
| Technical Specifications | Manual Operating Force | — | 176 ± 19 N | 176 ± 19 N |