Compact Bypass Switchgear for Power Distribution Systems
Compact bypass switchgear for power distribution and utility engineering. Practical layout and dependable operation support maintenance, retrofit, and network switching work.
As a professional manufacturer of By-pass Switchgear, we provide more cost-effective products. Whether you want to buy or become a distributor, you are welcome to contact us anytime.
Bypass switchgear is designed for power distribution systems that need compact switching equipment with practical field performance and dependable structure. This bypass switchgear supports maintenance access, temporary circuit transfer, and project-based utility work where equipment organization and installation efficiency are important. The overall arrangement is suitable for distribution applications that require a clean and practical switchgear solution.
For system upgrades, network branch projects, and engineering installations, the bypass switchgear offers a useful balance of compact design and operational convenience. It is suitable for contractors, distributors, and equipment integrators who need a product that can fit utility work and engineered layouts. The structure supports practical use in daily field conditions while keeping the product profile manageable.
This bypass switchgear is a good option for buyers looking for project-ready switchgear equipment with strong sourcing value and flexible application potential. It is suitable for power distribution maintenance, retrofit work, and long-term distributor cooperation.
Section |
Item | Detail | 12 kV | 24 kV |
| Model Selection | 200 A | Manual Operation | DPSW-FLW-12/T200-40 | DPSW-FLW-24/T200-40 |
| Model Selection | 200 A | Electric Operation | DPSW-FLW-12/200-40 | DPSW-FLW-24/J200-40 |
| Model Selection | 400 A | Manual Operation | DPSW-FLW-12/T400-40 | DPSW-FLW-24/T400-40 |
| Model Selection | 400 A | Electric Operation | DPSW-FLW-12/J400-40 | DPSW-FLW-24/J400-40 |
| Technical Specifications | Rated Current | — | 400/200 A | 400/200 A |
| Technical Specifications | Rated Frequency | — | 50/60 Hz | 50/60 Hz |
| Insulation Performance | Rated Impulse Withstand Voltage | Phase-to-Ground | 75 kV | 125 kV |
| Insulation Performance | Rated Impulse Withstand Voltage | Between Terminals of the Same Phase | 95 kV | 145 kV |
| Insulation Performance | Rated Power-Frequency Withstand Voltage | Phase-to-Ground | 42 kV | 64 kV |
| Insulation Performance | Rated Power-Frequency Withstand Voltage | Between Terminals of the Same Phase | 48 kV | 79 kV |
| Switching Current Capability | Load Current | — | 400/200 A | 400/200 A |
| Switching Current Capability | Magnetizing Current | — | 21 A | 21 A |
| Switching Current Capability | Cable Charging Current | — | 25 A | 25 A |
| Switching Current Capability | Line Charging Current | — | 1.5 A | 1.5 A |
| Technical Specifications | Rated Short-Time Withstand Current | — | 16 kA / 3 s | 16 kA / 3 s |
| Technical Specifications | Rated Closing Current | — | 50 kA | 50 kA |
| Gas Pressure | Rated Pressure | — | 0.5 ± 0.1 kgf/cm² | 0.5 ± 0.1 kgf/cm² |
| Gas Pressure | Explosion-Proof Pressure | — | 4–6 kgf/cm² | 4–6 kgf/cm² |
| Technical Specifications | Manual Operating Force | — | 176 ± 19 N | 176 ± 19 N |
WebLink:
Internallinking:
Shop